Feature | Value |
---|---|
Telemetering channels | |
Number of current metering channels |
4 |
Number of voltage metering channels |
4 |
Current channel metering range, A: - measurement transformers - protective transformers |
0.01 ÷ 50 0.05 ÷ 200 |
Metering range of voltage channels, V |
5.75 ÷ 440 |
Metering ranges of alternating current frequency, Hz |
from 42.5 to 57.5 |
Limits of permissible basic relative error of voltage metering, % |
±0.1 |
Limits of permissible basic relative error of AC amperage metering, % |
± 0.1 (at I <10 A) ± 0.5 (at I ≥ 10 A) |
Limits of permissible absolute error of AC frequency metering, Hz |
±0.01 |
Verification frequency, years |
10 |
Ethernet interfaces | |
Ports |
up to 16, depending on the version |
Baud rate, Mbit/s |
up to 1000 |
Design variants |
RJ-45, LC (single-/multi-mode), SFP |
Data exchange protocols |
IEC 60870-5-104; SV 61850-9-2 |
Network redundancy protocols |
PRP |
Clock synchronization protocol |
PTP, PPS |
Power supply | |
Power supply voltage, V - LV version - HV version |
12 ÷ 58 90 ÷ 264 |
Design | |
Case |
IP 20 plastic |
Mounting |
DIN rail 35 mm |
Overall dimensions (WxHxD) |
depending on the version |
Weight, kg, max |
1 |
Reliability | |
Mean time between failures, h |
140,000 hours |
Average lifetime |
30 years |
Operating environment | |
Ambient air temperature, °С |
-40 to +70 |
Relative humidity (non-condensing), % |
5 ÷ 95 at 30 °C |
Air pressure, kPa |
60 ÷ 106.7 |
TOPAZ TM PM7–A-[B1- to -Bx]-[C]-[D1- to -Dx]-[E1-to -Ex]-[F]-[G]-[K]-[L]-M-Pr | ||
Position | Code | Description |
Modification (set of functions) | ||
A | W | Measurement of electric parameters. Electricity metering. |
E | Measurement of electric parameters. Electricity metering. Basic electricity quality indicators based on GOST 32144-2013. Oscilloscope record. Detection of short circuits and steady-state line-to-ground faults. | |
D | Measurement of electric parameters. Electricity metering. Detection of short circuits, steady-state and alternating line-to-ground faults. | |
Q | Measurement of electric parameters. Electricity metering. Power quality indicators (full list). | |
LW | Measurement of electric parameters. Option to power the device using voltage measurement circuits. | |
Ethernet communication ports | ||
В1 to Bx | nGTx | Ethernet 1000 Mbit/s TX RJ45 |
nGSFP | Ethernet 1000 Mbit/s SFP | |
nGTXSFP | Ethernet 1000 Mbit/s combo-port RJ45/SFP | |
nTx | Ethernet 100 Mbit/s TX RJ45 | |
nFxS | Ethernet 100 Mbit/s FX LC single-mode | |
nFxM | Ethernet 100 Mbit/s FX LC multi-mode | |
n – number of Ethernet ports of the respective type | ||
RS-485 communication ports | ||
C | nR | RS-485, where n is the number of ports |
Discrete inputs/outputs | ||
D1 to Dx | nDI | Discrete inputs, where n is the number of discrete inputs. Increment – 8. |
nDOS | Discrete outputs of the signal relay type, where n is the number of discrete outputs. Increment – 8. | |
nDOC | Discrete outputs of the control relay type, where n is the number of discrete outputs. Increment – 3. | |
Design based on analog measurement circuits | ||
E1 to Ex | UI | Fixed set of analog channels |
nU | AC voltage measurement channels | |
nUDC | DC voltage measurement channels | |
nIMC | AC measurement channels with a range of up to 50A | |
nIPC | AC measurement channels with a range of up to 200A | |
nEMC | AC measurement channels with remote sensors and extended range of up to 50A | |
nEPC | AC measurement channels with remote sensors and range of up to 200A | |
nEPCО | AC measurement channels with remote connector sensors and extended range of up to 200A | |
Design variants based on analog measurement circuits can be found in the table below | ||
Information exchange protocols (in addition to basic protocols) | ||
F | IEC81 | IEC 61850-8-1 |
G | PRP | PRP redundancy protocol support |
Real-time clock | ||
H | RTC | Non-volatile real-time clock |
Additional options | ||
I | SSDm | SSD drives, where m is the total ROM volume of SSD drives in gigabytes (terabytes) |
SSDmT | ||
J | GNS | Built-in GPS/GLONASS reciever |
K | GSM | Built-in GSM modem |
L | PAN | Design variant with a built-in indicator for integrating into a panel |
Built-in power supply | ||
M | LV | One power supply input Urat = 24V DC |
2LV | Two power supply inputs Urat = 24V DC | |
HV | One power supply input 220V DC/AC | |
2HV | Two power supply inputs 220V DC/AC |
Module design variants based on analog measurement channels
Design version | Set of measurement channels | Supported modifications |
Basic design variant with a fixed set of analog channels | ||
UI | 3 AC voltage measurement channels with a common neutral wire |
PM7-W, PM7-E |
3 channels of phase current measurement; built-in measurement current transformer | ||
Current measurement channel for connecting an external core balance current transformer | ||
Design variants with a custom set of analog channels | ||
4U-4IMC |
4 alternating voltage channels, 4 alternating current channels |
PM7-D, PM7-Q |
4U-4IPC | ||
4U-3IPC-1IMC | ||
4U-4EMC | ||
4U-4EPC | ||
4U-3EPC-1EMC | ||
4U-4EPCO | ||
3U-1EMC |
3 alternating voltage channels, 1 alternating current channel |
PM7-LW |
3U-1EPC |