RS-485 interface parameters | |
Number of channels | 1 |
Baud rate, bit/s: | up to 115,200 |
Optical interface parameters | |
Number of channels | 1 |
Optical connector type | SC |
Optical fiber, μм | single-mode 9/125 μm |
Baud rate, kbaud, max. | 1000 |
Transfer range, min., m | 2000 |
Mains specifications | |
Power channels | 2 |
Rated supply voltage, V | 24 (DC) |
Operating supply voltage range, V | 15 ÷ 30 |
Current consumption (at 24 V), mA | 80 |
Design | |
Mounting type | DIN rail 35 mm |
Case material | plastic |
Case protection class | IР20 |
Module dimensions (width х height х depth), mm | 22.5 x 99 x 117 |
Weight, kg | 0,5 |
Reliability performance | |
Mean time between failures, h | 140000 |
Average time to restore operability at the operation facility (excluding the time of personnel arrival and if spare parts are available), min, max. | 30 |
Average service life, years | 30 |
Operating environment: | |
Ambient air temperature, 0С | -40 to +70 |
Average humidity (non-condensing), % | 5 ÷ 95 at 30 °C |
Air pressure, kPa | 60 ÷ 106.7 |