| 8 analog input channels (current/voltage), RS-485 | ||
| Analog input channels | ||
| Number of channels | 8 | |
| Measuring range (DC): | ||
| - current, mA | 0 ÷ 20, 4 ÷ 20 | |
| - voltage, V | 0 ÷ 10, 0 ÷ 5 | |
| Input impedance for mode, kOhm: | ||
| - measuring I | 0,1 | |
| - measuring U | 100 | |
| Signal threshold level: | ||
| - measuring I | 500 mA | |
| - measuring U | 150 V | |
| Verification period, years | 10 | |
| RS-485 interface | ||
| Ports | 1 | |
| Baud rate, bit/s: | up to 115,200 | |
| RS-485 interface communication protocol | IEC 870-5-101, Modbus RTU | |
| Power supply | ||
| Power supply voltage | 24 (15 - 30) V | |
| Power consumption (at 24 V) | 3 VA | |
| Design | ||
| Case | IP 20 plastic | |
| Mounting | DIN rail 35 mm | |
| Overall dimensions (WxHxD) | 22.5 x 99 x 117 | |
| Weight, kg | 0,2 | |
| Reliability | ||
| Mean time between failures, h | 140,000 hours | |
| Average lifetime | 30 years | |
| Operating environment: | ||
| Ambient air temperature, 0С | -40 to +70 | |
| Average humidity (non-condensing), % | 5 ÷ 95 at 30 °C | |
| Air pressure, kPa | 60 ÷ 106.7 | |