| Feature | Value |
|---|---|
| Fire and security alarm channels | |
|
Number of channels |
2 |
|
Controlled voltage ranges |
5 |
|
Maximum permissible current flowing through the terminals of the fire alarm loops, mA |
50 |
| Discrete input channels | |
|
Number of channels |
5 |
|
Type of connected sensors |
passive, dry contact |
| Telecontrol channels | |
|
Number of channels |
4 |
|
Type of outputs |
mechanical relay - 2, open collector - 2 |
| External reader channels | |
|
Number of channels |
2 |
|
Output interface |
TOUCH Memory and others |
|
Type of connected readers |
proximity cards |
|
Data interface |
Wiegand 26 |
| RS-485 communication interface | |
|
Baud rate, bit/s |
up to 115,200 |
|
Data exchange protocol |
IEC 870-5-101 |
| Mains specifications | |
|
Rated supply voltage, V |
24 (DC) |
|
Rated supply voltage range, V |
15 ÷ 30 |
|
Current (at 24 V), mA |
150 |
| Design | |
|
Mounting type |
DIN rail 35 mm |
|
Case material |
plastic |
|
Case protection class |
IР20 |
|
Module dimensions (width х height х depth), mm |
22.5 x 99 x 114.5 |
|
Weight, kg |
0.3 |
| Reliability performance | |
|
Mean time between failures, h |
140,000 |
|
Average recovery time at the operation site (excluding the time of personnel arrival and provided that spare parts are available), minutes, max. |
30 |
|
Average service life, years |
30 |
| Operating environment | |
|
Ambient air temperature, °С |
-40 to +70 |
|
Relative humidity (non-condensing), % |
5 ÷ 95 at 30 °C |
|
Air pressure, kPa |
60 ÷ 106.7 |