Feature | Value |
---|---|
Remote control channels | |
Number of channels | 6 (2 groups, 3 channels each) |
Switching voltage, V | 250 (AC), 350 (DC) |
Load capacity of control circuits, A, max.: | |
continuously | 1 |
1 s | 5 |
0.3 s | 15 |
0.03 s | 40 |
RS comand action time, s | 0.1 ÷ continuously |
Number of operations under load, min. | 100000 |
RS-485 communication interfaces | |
Ports | 2 |
Baud rate, bit/s: | up to 115,200 |
RS-485 interface communication protocol | IEC 870-5-101, Modbus RTU |
Mains specifications | |
Rated supply voltage, V | 24 (DC) |
Operating supply voltage range, V | 15 ÷ 30 |
Current consumption (at 24 V), mA | 180 |
Cold start time, max., s | 2 |
Design | |
Mounting type | DIN rail 35 mm |
wall | |
Case material | metal |
Case protection class | IР20 |
Module dimensions (width х height х depth), mm | 106x100x70 |
Weight, kg | 0,5 |
Reliability performance | |
Mean time between failures, h | 140000 |
Average time to restore operability at the operation facility (excluding the time of personnel arrival and if spare parts are available), min, max. | 30 |
Average service life, years | 30 |
Operating environment: | |
Ambient air temperature, 0С | -40 to +70 |
Average humidity (non-condensing), % | 5 ÷ 95 at 30 °C |
Air pressure, kPa | 60 ÷ 106.7 |