Feature | Value |
---|---|
Remote signalling channels | |
Number of channels | 8 |
RS sensor scanning period, ms | 0.5 ÷ 10 |
Discrete input channel input voltage, V | 5 ÷ 220 (AC/DC) |
Maximum input voltage, V | 400 |
Starting current (10 ms), mA | 20 |
Input current, A | 1 ÷ 10 |
Integrated power supply | 12 V, 200 mA |
Input impedance, kOhm, at U: | |
5 ÷ 48 V | 0.5 ÷ 9.6 |
48 ÷ 100 V | 16 ÷ 50 |
100 ÷ 220 V | 50 ÷ 220 |
Rated value of input currents, mA, at U: | |
5 ÷ 48 V | 5 ÷ 10 |
48 ÷ 100 V | 2 ÷ 3 |
100 ÷ 220 V | 1 ÷ 3 |
Telemetry channels | |
Number of current measurement channels | 3 |
Rated value of measured current (Ia, Ib, Ic), A | 1 5 |
Current measurement range, A | 0.01…1.5Irat |
Maximum value of measured current (Ia, Ib, Ic), A | 7,5 |
Power consumption of current circuits in nominal mode (for each phase), VA, max. | 0,3 |
Number of voltage measurement channels | 3 |
Rated value of measured alternating voltage (phase/linear), V | 57.7 / 100 |
230 / 400 | |
Phase voltage range of measurement, V | 0.3…1.2Urat |
Power consumption of voltage circuits in nominal mode (for each phase), VA | 0,1 |
Verification period, years | 10 |
Voltage discrete control channels | |
Number of channels | 3 |
Controlled voltage for each phase, V | 1 ÷ 310 (AC/DC) |
Input impedance, MOhm | 3,6 |
Remote control channels | |
Number of channels | 3 |
Switching voltage, V | 250 (AC), 350 (DC) |
Load capacity of control circuits, A, max.: | |
continuously | 1 |
1 s | 5 |
0.3 s | 15 |
0.03 s | 40 |
RS comand action time, s | 0.1 ÷ continuously |
Number of operations under load, min. | 100000 |
RS-485 communication interfaces | |
Ports | 2 |
Baud rate, bit/s: | up to 115,200 |
RS-485 interface communication protocol | IEC 870-5-101, Modbus RTU |
Mains specifications | |
Rated supply voltage, V | 24 (DC) |
Operating supply voltage range, V | 15 ÷ 30 |
Current consumption (at 24 V), mA | 150 |
Cold start time, max., s | 2 |
Design | |
Mounting type | DIN rail 35 mm |
using a bracket | |
Case material | metal |
Case protection class | IР51 |
Module dimensions (width х height х depth), mm | 100 x 120 x 50 |
Weight, kg | 0,6 |
Reliability performance | |
Mean time between failures, h | 140000 |
Average time to restore operability at the operation facility (excluding the time of personnel arrival and if spare parts are available), min, max. | 30 |
Average service life, years | 30 |
Operating environment: | |
Ambient air temperature, 0С | -40 to +70 |
Average humidity (non-condensing), % | 5 ÷ 95 at 30 °C |
Air pressure, kPa | 60 ÷ 106.7 |
The designation structure of TOPAZ HVD3 series devices is shown below.
TOPAZ HVD3-Х, where Х is device modification:
TOPAZ HVD3-RTU1 |
Performs the functions of RS and RC. 8 RS channels, 3 discrete voltage control channels 3 RC channels, 2 RS-485 channels |
TOPAZ HVD3-RTU3 |
Performs the functions of RS, RC, and TM. 1 current measurement channel, 3 voltage measurement channels, 8 RS channels, 3 discrete voltage control channels 3 RC channels, 2 RS-485 channels |
TOPAZ HVD3-RTU5 |
Performs the functions of RS, RC, TM and technical electricity metering. 3 current measurement channels with 3I0 calculation, 3 voltage measurement channels, 8 RS channels, 3 discrete voltage control channels 3 RC channels, 2 RS-485 channels
|
TOPAZ HVD3-ЕМ3 |
Performs the functions of RS, TM and technical electricity metering. 3 current measurement channels with 3I0 calculation, 3 voltage measurement channels, 8 RS channels, 3 discrete voltage control channels 2 RS-485 channels |
TOPAZ HVD3-RTU7 |
Performs the functions of RS, RC, TM and technical electricity metering. 4 current measurement channels, 3 voltage measurement channels, 12 RS channels, 3 discrete voltage control channels 3 RC channels, 2 RS-485 channels (copper/optic channel) |